Barksdale Temperature Switch L1X-H351S Single Setting Explosion Proof (4443)

Barksdale Temperature Switch L1X-H351S Single Setting Explosion Proof (4443)
$225 (USD)
Goleta, CA
orCall (805)-680-7222
Description
Barksdale Temperature Switch L1X-H351S
(4443)
Single setting, SPDT snap-action local mount,
Explosion-Proof
temperature Switch. Designed for Hazardous Areas, Class 1, Div. 1 & 2, Groups B, C, D; Class 2, groups E, F, G; Class 3. The Enclosure classifications are NEMA 4, 7, 9 and IP66 along with approvals UL and CSA.. Enclosed terminal strip with a tamper proof external adjustment. Switch is rated 10 amps 120 or 240 VAC.
Manufacturer: Barksdale
Model #: L1X-H351S
Model: Temperature Switch with Single Set Point
Description:This is a lightly used temperature switch. Explosion Proof. This item has an adjustable range of +100 to +225 Degrees F. The switch is also mounted to an assembly that has a custom hole for the shaft and two mounting port holes.
Defects: Cosmetic wear present, paint deteriation on the left side.
Specifications:
Media Temp Range:-100 to +400 F / -73 to +205 C
Adjustable Range: +100+225F/+38+107C
The following is taken from manufacturer's website:
Technical specifications
General Specifications*
Accuracy:
1% of mid-60% of full range. At constant ambient +/- 0.5% of full scale. (Knob indication is reference only)
Switch:
Single Setting:
Dual Setting:
One (1) single pole double throw (SPDT) circuit.
Electrical Characteristics:
All models incorporate Underwriters?? Laboratories, Inc. and CSA listed single pole double throw snap-action switching elements. Switches may be wired normally open or normally closed.
Wetted Parts:
304 stainless steel
Electrical Connection:
Single: 3-pin terminal strip
Electrical Ratings:
AC value at 75% power factor ?X10 amps 125, 250 volts AC, 3 amps 480 volts AC. Automatically reset by snap-action of switch.
Enclosure/Housing:
Designed for hazardous locations: Class I, Division 1 & 2
NEMA 4, 7, 9 & IP65 tamper-proof external adjustment, enclosed terminal strip.
Local Mount:
Immersion length 2-1/16 inches
Bulb & Capillary:
6 and 12 foot length standard.
Approvals:
UL (standard):
CSA (standard):
ATEX (optional):
Underwriters Laboratories, Inc. and Canadian Standard Assoc. are listed under Temperature indicating and regulating equipment, for use in hazardous locations, Class I, Groups B, C and D; Class II, Groups E, F and G.
File No. E58658, Guide No. XBDV
File No. LR34556,
Guide 400-E-O.8. Class 4868.
EX models are ATEX marked as follows:
CE 0081, ISSeP 08 ATEX024X
Ex II 2G D, Ex db IIC T6Gb
Ex tb IIIC T80C Db IP66
-40C Tamb +75C
Temperature Range:
See product confi gurator
Adjustment:
Tamper resistant external adjustment. Turn knob clockwise to increase setpoint. (Knob indication is reference only)
Standard Options/ Modifications:
For thermowels, split nuts and union connections, see accessory pages.
Weight:
Single - approximate 3.0 lbs..
* See Product Confi gurator for additional options.
Wiring Code
Lead
Circuit #1
Circuit #2
Normally Closed
Blue
Orange
Common
Purple
Brown
Normally Open
Red
Yellow
Sold as is with 30day Right of Return, only pictured items included
Easy return/refund for any reason
Anacapa Equipment
RETURNS
Anacapa Equipment strives to offer excellent customer service. You may return any equipment purchased from us for any reason within thirty (30) days after your receipt of the equipment for a full refund of the purchase price, provided that returned items must be received in the same condition as sent. We DO NOT ship internationally. IF you are using a freight forwarder then returns are VOID.
SHIPPING
All equipment purchased is shipped within one (1) day (subject to freight availability) after receipt of payment and is shipped FOB place of shipment. We only charge actual shipping cost. If eBay overcharges for shipping, we issue an immediate refund for the difference. If you are undercharged, we will absorb the cost.
We DO NOT ship internationally. IF you are using a freight forwarder then returns are VOID.
LIMITED WARRANTY
Buyer acknowledges that the equipment is being sold as is and without any warranty of merchantability or fitness for a particular use. Buyer may inspect the equipment prior to purchase and placement of the order prior to inspection is deemed a waiver of Buyers right to inspect. Buyer is responsible for determining the suitability of this product for its application. Anacapa Equipment Brokers, Inc. assumes no liability for the use or misuse of any equipment purchased by Buyer. It is assumed that the unit will be installed and operated by qualified personnel. The purchaser agrees that the seller shall not be held responsible or liable for any injuries or damages, whether incidental or consequential, associated in any way with the equipment purchased.
The Buyer, by purchasing this equipment, indicates its acknowledgment of, and agreement, to the terms of this limited warranty.
DISCLAIMER
This equipment is not intended to be used, and should not be used in human experimentation, nor should this instrument be applied to humans in any way.
Specifications
Manufacturer | Barksdale |
Model | Temperature Switch with Single Set Point |
Condition | Used |
Model # | L1X-H351S |
Defects | Cosmetic wear present, paint deteriation on the left side. |
Media Temp Range | -100 to +400 F / -73 to +205 C |
Adjustable Range | +100+225F/+38+107C |
Single | 3-pin terminal strip |
Designed for hazardous locations | Class I, Division 1 & 2 |