Omega CN8201-R1-C2 1/16 Din Universal Temp & Process Controller USED (9807) M

No longer available

Omega CN8201-R1-C2 1/16 Din Universal Temp & Process Controller USED (9807) M

$190 (USD)

Goleta, CA

Description

Omega Engineering CN8201-R1-C2 1/16 Din Universal Temp & Process Controller (9807) M In good cosmetic condition. See pictures for more detail. Manufacturer: Omega Engineering Model: CN8201-R1-C2 Specifications: The following specifications were taken from an online user manual or manufacturer's website and may not be specific to this item, please look at pictures carefully for items included and specifics. These specifications are for reference only. Field-Configurable Universal Inputs Autotuning, Direct or Reverse-Acting for Both Outputs User-Selectable Ramp to Setpoint 8 Ramp and 8 Soak Segments Standard Features: Field-Configurable Universal Inputs Autotuning, Direct- or Reverse-Acting for Both Outputs User-Selectable Ramp to Setpoint U 8 Ramp and 8 Soak Segments U Decimal Display in 0.1 for Measured Temperatures Under 1000F or C U NEMA 4X (IP65) Front Panel Actual dimensions: 8x4x4" weight: 3 lbs The CN8200 temperature/process controller is extremely versatile and user-friendly. The operator needs to review only those parameters relevant to the particular application during setup. A dual digital display offers optimum process information at a glance. Individual LED's identify the status of outputs, alarms, digital communications, and special options. The CN8200 features a NEMA-4X front panel and a universal power supply that accepts 100 to 250 Vac and 120 to 250 Vdc. A 24 Vac/24 Vdc power supply option is also available. Control algorithms available are P, PI, PD, PID, or ON/OFF. The autotune feature automatically sets proportional band, derivative, and integral before the process reaches setpoint. These parameters provide quick stabilization of processes with minimum overshoot, hunting, or cycling. Eight-level ramp/soak control consisting of 8 ramps and 8 soaks is standard, and includes a decimal display on thermocouple ranges, digital display and signal filtering, and a percentage of power limit setting. The dual control outputs can be configured for a variety of control and alarm applications, and two dedicated alarm outputs are also available. The CN8200 offers a wide range of options, including RS-232 and RS-485 digital communications, five remote analog setpoint ranges, three contact/digital input modes, four transducer excitation voltages, and four auxiliary output ranges. Specifications Performance Accuracy: 0.2% of full scale, 1 digit Setpoint Resolution: 1 count/0.1 count Repeatability: 1 count Temperature Stability: 5 V/C (maximum) TC Cold-Junction Tracking: 0.05C/C ambient Common Mode Rejection: 100 dB Series Mode Rejection: >70 dB Process Sampling: 10 Hz (100 ms) Inputs Input Type: See Input Table Digital Input: For remote setpoint, remote standby or ramp/soak run and hold Thermocouple Lead Resistance: 100 ohms max for rated accuracy Decimal Position: Selectable Outputs Output #1: Reverse or directacting, configured from menu Output #2: Reverse or directacting, configured from menu Mechanical Relay: Rated 5 A @120 Vac, 3 A @ 240 Vac, normally open (N.O.), normally closed (N.C.), (output 1); Rated 5 A @120 Vac, 3 A @ 240 Vac, N.O. (output 2) Current: 4 to 20 mA, 500 ohm max (suffix F1, F2); 4 to 20 mA, 1000 ohm max (suffix FH1, FH2) Voltage: 20 Vdc pulse Solid State Relay: SSR, 120/240 Vac, zero voltage switched, rated 1 A continuous, 10 A surge @ 25C Alarms: Mechanical relay rated 5 A @ 120 Vac, 3 A @ 240 Vac, N.O.; Optically isolated SSR rated 1 A, 120/240 Vac @ 25C; dc alarms, 24 Vdc Transducer Power Supply: 5, 10, 12, 15 Vdc 10% Control Characteristics Setpoint Limits: Limited to configured range for thermocouple and RTD; limited to scaled range Alarms: Adjustable for high/low; selectable process or deviation Rate (Derivative): 0 to 2400 seconds Reset (Integral): 0 to 9600 seconds Cycle Time: 0.2 to 120 seconds Proportional Band: 1 to span of sensor Deadband: negative span to positive span of sensor Hysteresis: 1 to span of sensor Autotune Damping: Adjustable (low, normal, or high) Ramp to Setpoint: 1 to 9999 minutes Autotune: Operator-initiated from front panel Manual Control: Operator-initiated from front panel General Power: 100 to 250 V, 50/60 Hz (single-phase), 120 to 250 Vdc, 24 Vac/24 Vdc optional Display: Dual LED, 4-digit, orange: process display, green: menu/ parameter display; 9.2 mm (0.36') Power Consumption: Less than 6 VA (instrument) @ 120 Vac Weight: 226 g (8 oz) Panel Cutout: 45 mm (1.771') square Dimensions: 53.3 H x 53.3 W x 8.21 mm D (2.1 x 2.1 x 0.72') bezel Depth Behind Panel: 100 mm (3.937') Front Panel Rating: NEMA-4X Operating Ambient Range: 0 to 55C (32 to 131F) Humidity: 90% RH max, non-condensing Memory Protection: Solid-state non-volatile memory Connections: Screw terminals Contacts: Twin bifurcated Ramp/Soak Programming Intervals: 8 Loops: 0 to 99 Ramp Time: 0 to 9999 minutes Soak Time: 0 to 9999 minutes Events/Alarms: 1 to 8 Ramp Setpoint: 1 to 9999 minutes CN8-SW (Optional Software) Minimum Hardware and Software Requirements: IBM PC or 100% compatible, Windows 95/98/NT; RS-485 interface or RS-232 to RS-485 converter Software Compatibility: CN8200 Series controllers Software Capability: Supports up to 254 CN8200 Series controllers. Dimensions Actual Dimensions: 8x4x4" Actual Weight: 3 lbs Sold as is with 30day Right of Return, only pictured items included Easy return/refund for any reason Anacapa Equipment RETURNS Anacapa Equipment Brokers, Inc. (Seller) strives to offer excellent customer service. You may return any equipment purchased from us for any reason within thirty (30) days after your receipt of the equipment for a full refund of the purchase price, provided that returned items are received in the same condition as sent. We DO NOT ship internationally. If you are using a freight forwarder then returns are VOID. SHIPPING All equipment purchased is shipped within one (1) business day (subject to freight availability) after receipt of payment and is shipped FOB place of shipment. We only charge actual shipping cost. If eBay overcharges for shipping, we issue an immediate refund for the difference. If you are undercharged, we will absorb the cost. We DO NOT ship internationally. IF you are using a freight forwarder then returns are VOID. LIMITED WARRANTY Buyer acknowledges that the equipment is being sold as is" and without any warranty of merchantability or fitness for a particular use. The entire risk as to the quality and performance of the equipment is with the Buyer. Should the equipment prove defective following its purchase the Buyer and not the Seller, manufacturer, distributor, or retailer assumes the entire cost of all necessary servicing or repair. Buyer may inspect the equipment prior to purchase and placement of the order. Failure to inspect prior to placement of an order is deemed a waiver of Buyers right to inspect. Buyer is responsible for determining the suitability of the equipment for its application. Seller assumes no liability for the use or misuse of any equipment purchased by Buyer. It is assumed that the equipment will be installed and operated by qualified personnel. The Buyer agrees that the Seller shall not be held responsible or liable for any injuries or damages, whether incidental or consequential, associated in any way with the equipment purchased. The Buyer, by purchasing this equipment, indicates its acknowledgment of, and agreement, to the terms of this limited warranty . INDEMNITY Buyer shall be solely liable for, and shall defend, indemnify, and hold Seller, its Affiliates, and all of their respective directors, officers, employees, agents, and independent contractors (Indemnitees) harmless from and against any and all damages, liabilities, injuries, losses, costs (including reasonable attorneys and experts fees at trial and on appeal), and expenses which may be incurred by, asserted against, or recoverable from any Indemnitee as a result of any actual or threatened action, suit or proceeding arising out of or relating in any way to the purchase of equipment from Seller. The validity and interpretation of this Agreement and the enforcement thereof shall be governed by the laws of the State of California without regard to any principles governing conflicts of laws. Any dispute arising from the purchase of equipment from Seller must be resolved in the State Courts of California.

Specifications

ManufacturerOmega Engineering
ModelCN8201-R1-C2
ConditionUsed
SpecificationsThe following specifications were taken from an online user manual or manufacturer's website and may not be specific to this item, please look at pictures carefully for items included and specifics. These specifications are for reference only.
Actual dimensions8x4x4"
Weight226 g (8 oz)
Accuracy0.2% of full scale, 1 digit
Setpoint resolution1 count/0.1 count
Repeatability1 count
Temperature stability5 V/C (maximum)
Tc cold-junction tracking0.05C/C ambient
Common mode rejection100 dB
Series mode rejection>70 dB
Process sampling10 Hz (100 ms)
Input typeSee Input Table
Digital inputFor remote setpoint, remote standby or ramp/soak run and hold
Thermocouple lead resistance100 ohms max for rated accuracy
Decimal positionSelectable
Output #1Reverse or directacting, configured from menu
Output #2Reverse or directacting, configured from menu
Mechanical relayRated 5 A @120 Vac, 3 A @ 240 Vac, normally open (N.O.), normally closed (N.C.), (output 1); Rated 5 A @120 Vac, 3 A @ 240 Vac, N.O. (output 2)
Current4 to 20 mA, 500 ohm max (suffix F1, F2); 4 to 20 mA, 1000 ohm max (suffix FH1, FH2)
Voltage20 Vdc pulse
Solid state relaySSR, 120/240 Vac, zero voltage switched, rated 1 A continuous, 10 A surge @ 25C
AlarmsAdjustable for high/low; selectable process or deviation
Transducer power supply5, 10, 12, 15 Vdc 10%
Setpoint limitsLimited to configured range for thermocouple and RTD; limited to scaled range
Rate (derivative)0 to 2400 seconds
Reset (integral)0 to 9600 seconds
Cycle time0.2 to 120 seconds
Proportional band1 to span of sensor
Deadbandnegative span to positive span of sensor
Ramp to setpoint1 to 9999 minutes
AutotuneOperator-initiated from front panel
Manual controlOperator-initiated from front panel General
Power100 to 250 V, 50/60 Hz (single-phase), 120 to 250 Vdc, 24 Vac/24 Vdc optional
Power consumptionLess than 6 VA (instrument) @ 120 Vac
Panel cutout45 mm (1.771') square
Dimensions53.3 H x 53.3 W x 8.21 mm D (2.1 x 2.1 x 0.72') bezel
Depth behind panel100 mm (3.937')
Front panel ratingNEMA-4X
Operating ambient range0 to 55C (32 to 131F)
Humidity90% RH max, non-condensing
Memory protectionSolid-state non-volatile memory
ConnectionsScrew terminals
ContactsTwin bifurcated
Intervals8
Loops0 to 99
Ramp time0 to 9999 minutes
Soak time0 to 9999 minutes
Events/alarms1 to 8
Ramp setpoint1 to 9999 minutes
Minimum hardware and software requirementsIBM PC or 100% compatible, Windows 95/98/NT; RS-485 interface or RS-232 to RS-485 converter
Software compatibilityCN8200 Series controllers
Software capabilitySupports up to 254 CN8200 Series controllers.
Actual weight3 lbs